Sänkta ventilationsflöden på Sundsvalls sjukhus: Utvärdering av ett energibesparingsinitiativ genom rökförsök och temperaturmätningar
Mid Sweden University, Faculty of Science, Technology and Media, Department of Chemical Engineering.
2017 (Swedish)Independent thesis Basic level (professional degree), 10 credits / 15 HE creditsStudent thesis
Abstract [sv]

I syfte att sänka energianvändningen på Sundsvalls sjukhus riktas nu fokus mot ventilationssystemet och möjligheterna att där sänka luftflöden. Denna uppsats undersöker detta energibesparingsinitiativ genom att studera vad som händer med luftrörelser och temperaturer i ett rum på sjukhuset vid varierande ventilationsflöden. Metoden är rökförsök med observation och analys av mätdata som jämförs med krav på inomhusklimat och beräkningar av temperatureffektiviteten, ett kvantitativt mått på hur väl tillförd värme kommer rummets vistelsezon tillgodo. Resultaten indikerar bland annat att det kan vara till nackdel för luftkvalitén med alltför drastiska ventilationsflödessänkningar i det observerade rummet, detta fastän mängden tillförd luft är mer än tillräcklig enligt gällande krav. Bäst temperatureffektivitet uppnås då frånluft går via både frånluftsdon och frånluftsfönster vilket pekar mot att bäst förutsättningar för att sänka ventilationsflöden eller tilluftstemperatur finns med denna frånluftsinställning.

Abstract [en]

With the purpose of lowering energy consumption at Sundsvall Hospital, focus is now being directed towards the ventilation system and the possibility to reduce air flow. The thesis examines this energy-saving initiative by studying what happens to air movements and temperatures in one room at the hospital when ventilation air flow is varied. Air movements were made visible with smoke and observed and temperatures were logged. Observations and data were then analyzed with regard to indoor climate requirements and temperature efficiency, a quantitative measure of how well supplied heat will benefit a room’s occupied zone. The results indicate, among other things, that a too great reduction in air flow rates can have a negative impact on the air quality in the observed room, even though the amount of air supplied is more than sufficient according to current requirements. Best temperature efficiency is achieved when exhaust air passes through both the exhaust air device and the ventilated windows, indicating that this is the most favorable exhaust air setting for lowering ventilation air flow rates or room supply air temperature.

Place, publisher, year, edition, pages
2017.
Keywords [en]
Sundsvall Hospital, Sundsvall Regional Hospital, indoor climate, airborne heating, air heating, temperature efficiency
Keywords [sv]
Sundsvalls sjukhus, Länssjukhuset Sundsvall-Härnösand, inomhusklimat, luftburen värme, luftvärme, temperatureffektivitet.
National Category
Energy Engineering
Identifiers
URN: urn:nbn:se:miun:diva-31040Local ID: ER-V17-G3-005OAI: oai:DiVA.org:miun-31040DiVA, id: diva2:1116857
Subject / course
Energy Technology EN2
Educational program
Energy Engineering TENIG 180 higher education credits
Supervisors
Examiners
Available from: 2017-06-28 Created: 2017-06-28 Last updated: 2017-06-28Bibliographically approved

Open Access in DiVA

fulltext(2831 kB)808 downloads
File information
File name FULLTEXT01.pdfFile size 2831 kBChecksum SHA-512
4d554c03e4633f79eca50c2a5b74ac2653225132742e7797de9d3968e52cc7e9bf5384f53cc6a03216a4fe3a73f4b528e14bad3b330b0039ea5a21c11cc0f08a
Type fulltextMimetype application/pdf

Search in DiVA

By author/editor
Wickström, Johan
By organisation
Department of Chemical Engineering
Energy Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 809 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

urn-nbn

Altmetric score

urn-nbn
Total: 409 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf