Livcykelkostnad för ventilationssystem: En jämförelse mellan konventionell och hög luftomsättning för ökad kognitiv förmåga
Mid Sweden University, Faculty of Science, Technology and Media, Department of Chemical Engineering.
2016 (Swedish)Independent thesis Basic level (professional degree), 10 credits / 15 HE creditsStudent thesis
Abstract [sv]

I detta examensarbete har två ventilationssystem konstruerats och jämförts gällande dimensionering, investerings- och livscykelkostnader. Alternativ A har utformats för konventionell luftomsättning medan alternativ B har utformats för att hantera en relativt hög luftomsättning. Idén till jämförelsen kom från ny forskning som har visat på att en relativt hög luftomsättning och resulterande lägre koldioxidhalt kan ha stor inverkan på den kognitiva förmågan hos individerna inom systemet. Utformning och dimensionering av systemen har gjorts med hjälp av programvarorna MagiCAD och Pro Unit. Arbetet har visat på tydliga skillnader i dimensioneringen av respektive system. Alternativ B kräver mer utrymme än alternativ A. I vissa delar av systemet är det till och med tveksamt om alternativ B är praktiskt möjligt att installera på grund av sitt behov av större kanaldimensioner. När det gäller investeringskostnad så har det under detta arbete visat sig att alternativ A är ungefär 30 % billigare än alternativ B om projektering, rivning av befintligt system, installation och material tas i beaktande. Detta var en oväntat liten prisskillnad i förhållande till den förväntade, men eftersom vissa delar av ventilationssystemet inte är inkluderade i konstruktionerna, som till exempel kanaler för ute- och avluft samt motoriserade spjäll för variabelt flödesbehov kan skillnaden i den slutgiltiga investeringskostnaden visa sig bli större i framtiden för alternativ B. Jämförelsen mellan livscykelkostnad för alternativen är central i detta arbete. En modell för att beräkna livscykelkostnader för respektive system har skapats i Excel. Livscykelskostnadsmodellen visar att alternativ B kan vara mer ekonomiskt fördelaktigt redan vid små tilläggskostnader för minskad kognitiv förmåga för alternativ A. Avslutningsvis så pekar detta examensarbete på att mer forskning behövs angående hur luftomsättning i ventilationssystem påverkar kognitiv förmåga hos individer inom systemet samt vilka konsekvenser och möjligheter detta kan innebära.

Abstract [en]

In this thesis two different ventilation systems have been designed and compared due to design, investment costs and life cycle costs. Option A was designed for conventional air circulation while Option B was designed to handle a relatively high air circulation. The idea for comparison came from new research that shows that a relatively high air flow and resulting lower carbon dioxide levels can have a big impact on the cognitive abilities of individuals within the system. Design and dimensioning of the systems has been done with software such as MagiCAD and Pro Unit. The work has shown clear differences in the design of each system. Option B requires much more space than option A. In some parts of the system, it is doubtful that alternative B is practical to install because of its needs for larger channel dimensions. Regarding the investment costs for each option this work has shown that option A is about 30% cheaper than alternative B when differences in design, demolition of existing parts, installation and new materials had been taken into consideration. This was a surprisingly small price difference in relation to what was expected. The comparison between life cycle costs of the two different alternatives has been a central part of this work. A model for calculating the life cycle costs of each system was created in Excel and the model showed that systems with relatively high air circulation could be preferable even at small additional costs for reduced cognitive performance for conventional flow systems. This thesis points out that more research is needed on how the air circulation in the ventilation system affects the cognitive skills of individuals within the system.

Place, publisher, year, edition, pages
2016. , p. 38
Keywords [sv]
Luftomsättning, kognitiv förmåga, livscykelkostnad, LCC, ventilationssystem, VVS
National Category
Energy Engineering
Identifiers
URN: urn:nbn:se:miun:diva-29848Local ID: ER-V16-G3-003OAI: oai:DiVA.org:miun-29848DiVA, id: diva2:1063785
Subject / course
Energy Technology EN2
Educational program
Energy Engineering TENIG 180 higher education credits
Supervisors
Examiners
Available from: 2017-01-11 Created: 2017-01-11 Last updated: 2017-01-11Bibliographically approved

Open Access in DiVA

fulltext(6591 kB)788 downloads
File information
File name FULLTEXT01.pdfFile size 6591 kBChecksum SHA-512
7a28d759bc62acfce0ed615af7fed37b0f040b99e4b8264f4e1ba55a7a31722d77ae0fe143133900fa45c7f60fe900b015e920eeb363579fa590f64618e6e4a3
Type fulltextMimetype application/pdf

Search in DiVA

By author/editor
Eriksson, Martin
By organisation
Department of Chemical Engineering
Energy Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 791 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

urn-nbn

Altmetric score

urn-nbn
Total: 561 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf